4.5.2 Settings for Power MeasurementItem Description1 Select unit and CH Select unit and CH to set.2 Phase/Wire system Select phase and wire system to power measurement.
1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)3 Cutoff current Set a ratio of current for rated current used for cutoff that is notmeasured.0.1 to 50.0% (initial:0.1)4 Hour meter Select phase andcurrent that is measured as ON-time bypercentage.
Target phase : Phase1, Phase2, Phase3, ALL (initial:Phase1)Threshold : 0.1 to 100.0% (initial:10.0)5 Simple measuring Select mode and set parameters for simple measuring.
Type:OFF (no use)VLT/PF Fixed (Use actual current with fixed voltage and PF)SingleCT (Use phase 1 current and all voltage)(initial:OFF)VLT* : 0.0 to 500000.0V (initial:230V)PF* : 0.000 to 1.000 (initial:1.000)* VLT and PF can be set when ‘VLT/PF Fixed’ is selected.1234 567891011Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.netBuy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com