Introduction16 192-120102 N7 - February 20042.6.2. Conditions of utilization for UL certificationUL certificationconform to UL: ! according to UL508CCertified ! E-File_No.: E235 342The UL certification is documented by a UL logo on thedevice (type specification plate)"UL" - logo:Conditions of utilization! The devices are only to be installed in a degree of contamination 2 environment(maximum).! The devices must be appropriately protected (e.g. by a switching cabinet).! The terminals are suitable for field wiring.! Tightening torque of the field wiring terminals (green Phoenix plugs)! C3SxxxV2 0.57-0.79Nm 5 - 7Lb.in! C3SxxxV4 exept C3S300V4 0.57-0.79Nm 5 - 7Lb.in! C3S300V4 1.25-1.7Nm 11 - 15Lb.in! Temperature rating of field installed conductors shall be at least 60∞C Usecopper conductors only. Please use the cables described in the accessorieschapter; they do have a temperature rating of at least 60∞C! Maximum ambient temperature: 45∞C.! Suitable for use on a circuit capable of delivering not more than 500 rmssymmetrical amperes, 400 volts maximum.ATTENTIONDanger of electric shock.Discharge time of the bus capacitator is 5 minutes.! The drive provides internal motor overload protection.This must be set so that 200% of the nominal motor current are not exceeded.! Cable cross-sections! Mains input: corresponding to the recommended fuses (see on page 51)! Motor cables: corresponding to the nominal output currents (see on page 51)! Maximum cross-section limited by the terminals mm 2 / AWG! C3SxxxV2 2.5mm 2 AWG 12! C3SxxxV4 exept C3S300V4 4.0mm 2 AWG 10! C3S300V4 6.0mm 2 AWG 7! Circuit protectionIn addition to the branch circuit protection, the devices have to be protected withthe supplementary protector S 261 L, manufactured by ABB.! C3S025V2: ABB, nominal 400V 10A, 6kA! C3S063V2: ABB, nominal 400V, 16A, 6kA! C3S038V4: ABB, nominal 400V, 10A, 6kA! C3S075V4: ABB, nominal 400V, 16A, 6kA! C3S150V4: ABB, nominal 400V, 20A, 6kA! C3S300V4: ABB, nominal 400V, 25A, 6kA! C3S300V4: ABB, nominal 400V, 25A, 6kA