Regency ® P33-10 Zero Clearance Direct Vent Gas Fireplace | 19|19installationTermination CapWall Thimble 2 pieces(10" (254mm) Outer Diameter)2” x 4” or 2” x 6”(21mm x 102mmor 21mm x 152mm)6-7/8"(175mm)dia. air intake4" (102mm)dia. flue pipewith spring spacerScrews(4 per connection)Screws(3 perconnection)Outside WallMur éxtérieurFurringStripsFourrures en boisFurstrp.epssee also c34020a.epsfurstrpf.epsfrenchINSTALLATION PROCEDURESfor Regency® Direct Vent System (Flex)Minimum and Maximum Vent Clearances1) Locate the unit in the framing, rough in thegas (preferably on the right side of the unit)and the electrical (Junction block is on theleft side) on the left. Locate the centerline ofthe termination and mark wall accordingly.Cut a 10"(254mm) hole in the wall (insidedimension).Note: To make the installation moreaesthetically pleasing, we recommendframing out a square to mount theterminal to.*If this is an outside corner, the minimum distance between the vent and the outsidecorner is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Dura-Venttermination cap. See "F" in the diagram in "Exterior Vent Trmination Locations" Section.Note: A 2-1/2" (64mm) horizontal top and1-1/2" (38mm) horizontal sides &bottom clearance around the linermust be maintained except that onlya 1" (25mm) clearance is needed atthe termination end. We recommendframing a 10"(254mm) x 10"(254mm)(inside dimensions) hole to givestructural rigidity for mounting thetermination.Note: If installing termination on a sidingcovered wall, furring strips must beused to ensure that the terminationis not recessed into the siding.2) Level the fireplace and fasten it to the framingusing nails or screws through the nailingstrips.3) Assemble the vent assembly by applyingMill Pac to the 4"(100mm) inner collar ofthe termination and slipping the 4"(100mm)liner over it at least 1-3/8" (35mm). Fastenwith the 3 screws (drilling pilot holes willmake this easier). Apply Mill-Pac to the6-7/8"(175mm) flex pipe and slip it overthe 6-7/8" outer collar of the vent terminalat least 1-3/8"(35mm) and fasten with the3 screws.4) Separate the 2 halves of the wall thimble andsecurely fasten the one with the tabs to theoutside wall making sure that the tabs areon top and bottom. Fasten the other thimblehalf to the inside wall. The thimble halvesslip inside each other and can be adjustedfor 2 x 4 or 2 x 6 walls. The liners must slipover the collars a minimum of 1-3/8".5) Slip the assembled liner and terminationassembly through the thimble making surethe termination cap faces up (there aremarkings on the cap that show which wayis up). This will position the termination capwith proper down slope for draining water.Fasten the cap to the outer wall with the 4supplied screws.6) Pull the centre 4"(100mm) liner and outer6-7/8"(175mm) liner out enough to slip overthe flue collars of the fireplace.7) Apply Mill Pac over the fireplace inner collarand slip the 4"(100mm) liner down over itand attach with 3 supplied screws.8) Do the same with the 6-7/8"(175mm) liner.9) Apply a bead of silicone between thethimble and termination and around theouter edge of the terminal at the wall inorder to keep the water out.IMPORTANT: Do not locate terminationhood where excessive snow or icebuildup may occur. Be sure to checkvent termination area after snowfalls, and clear to prevent accidentalblockage of venting system. Whenusing snow blowers, make suresnow is not directed towards venttermination area.