663 sec. 3 sec.9. Installer parametersTo enter installer parameters please follow steps below. Please refer to parameters table description before any changes. Use or buttons to moveup or down between all parameters. Every change/selection confirm by button:13Use or to choosecode „49”.Press button to confirm. Select installer parameter by orbuttons. Use or buttons tochange parameter value. Confirmchoice by button.42Hold + buttons for 3 secondsto enter the installer mode.dXX Function ParameterValues Description DefaultValuesd00 Temperature unit0 Celsius [°C]01 Fahrenheit [°F]d01The method of controlling thetemperature of the heatingsystem0 by TPI algorithm01 SPAN ±0.5°C2 SPAN ±1.0°Cd02 Correction of the displayedtemperaturefrom -3.0°Cto +3.0°CIf the thermostat indicates an incorrect temperature,it can be corrected by ± 3.0°C 0°Cd03 Floor temperature sensor use(S1,S2)0 No sensor01 Temperature sensor connected2 Dew point sensor connected (only in UFH)3 Occupancy sensor connected3