Vacon HVAC Application vacon • 3424-hour support +358 (0)201 212 575 • Email: vacon@vacon.com33.4 HVAC Application - Quick setup parameter groupThe Quick Setup parameter group is a collection of parameters that are most commonly usedduring installation and commissioning. They are collected in the first parameter group so thatthey can be found fast and easily. They can, however, be also reached and edited in their actualparameter groups. Changing a parameter value in the Quick setup group also changes thevalue of this parameter in its actual group.Table 30: Quick setup parameter groupIndex Parameter Min Max Unit Default ID DescriptionP1.1 Motor nominal voltage Varies Varies V Varies 110Find this value Un on therating plate of the motor.See page 48.P1.2 Motor nominalfrequency 8.00 320.00 Hz 50.00 111Find this value f n on therating plate of the motor.See page 48.P1.3 Motor nominal speed 24 19200 rpm Varies 112 Find this value nn on therating plate of the motor.P1.4 Motor nominal current Varies Varies A Varies 113 Find this value In on therating plate of the motor.P1.5 Motor Cos Phi 0.30 1.00 Varies 120 Find this value on the ratingplate of the motor.P1.6 Motor nominal power Varies Varies kW Varies 116 Find this value In on therating plate of the motor.P1.7 Motor current limit Varies Varies A Varies 107 Maximum motor currentfrom AC drive.P1.8 Minimum frequency 0.00 P1.9 Hz Varies 101 Minimum allowed frequencyreference.P1.9 Maximum frequency P1.8 320.00 Hz 50.00 102 Maximum allowed frequencyreference.P1.10 I/O control reference Aselection 1 8 6 117Selection of ref source whencontrol place is I/O A. Seepage 52 for selections.P1.11 Preset frequency 1 P3.3.1 300.00 Hz 10.00 105Select with digital input:Preset frequency selection 0(P3.5.1.15)(Default = Digital Input 4)P1.12 Preset frequency 2 P3.3.1 300.00 Hz 15.00 106Select with digital input:Preset frequency selection 1(P3.5.1.16)(Default = Digital Input 5)P1.13 Acceleration time 1 0.1 3000.0 s 20.0 103 Time to accelerate from zeroto maximum frequency.P1.14 Deceleration time 1 0.1 3000.0 s 20.0 104 Time to decelerate fromminimum to zero frequency.P1.15 Remote control place 1 2 1 172Selection of remote controlplace (start/stop)1 = I/O2 = FieldbusP1.16 Automatic reset 0 1 0 731 0 = Disabled1 = Enabled