3vacon • 63 Vacon HVAC ApplicationTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2053.6.8 Group 3.6: Fieldbus Data MappingFieldbus process data outValues to monitor through fieldbus are:Table 51: Fieldbus data mappingIndex Parameter Min Max Unit Default ID DescriptionP3.6.1 Fieldbus data out 1selection 0 35000 1 852Data sent to fieldbus can bechosen with parameter andmonitor value ID numbers.The data is scaled to unsigned16-bit format according to theformat on keypad. E.g. 25.5 onkeypad equals 255.P3.6.2 Fieldbus data out 2selection 0 35000 2 853 Select Process Data Out withparameter ID.P3.6.3 Fieldbus data out 3selection 0 35000 45 854 Select Process Data Out withparameter ID.P3.6.4 Fieldbus data out 4selection 0 35000 4 855 Select Process Data Out withparameter ID.P3.6.5 Fieldbus data out 5selection 0 35000 5 856 Select Process Data Out withparameter ID.P3.6.6 Fieldbus data out 6selection 0 35000 6 857 Select Process Data Out withparameter ID.P3.6.7 Fieldbus data out 7selection 0 35000 7 858 Select Process Data Out withparameter ID.P3.6.8 Fieldbus data out 8selection 0 35000 37 859 Select Process Data Out withparameter ID.Table 52. Fieldbus Process Data OutData Value ScaleProcess Data Out 1 Output frequency 0.01 HzProcess Data Out 2 Motor speed 1 rpmProcess Data Out 3 Motor current 0.1 AProcess Data Out 4 Motor torque 0.1 %Process Data Out 5 Motor power 0.1 %Process Data Out 6 Motor voltage 0.1 VProcess Data Out 7 DC-link voltage 1 VProcess Data Out 8 Last active fault code