3vacon • 69 Vacon HVAC ApplicationTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2053.6.12 Group 3.10: Automatic resetTable 56: Autoreset settingsIndex Parameter Min Max Unit Default ID DescriptionP3.10.1 Automatic reset 0 1 0 731 0 = Disabled1 = EnabledP3.10.2 Restart function 0 1 1 719The start mode for Automaticreset is selected with thisparameter:0 = Flying start1 = According to par. P3.2.4P3.10.3 Wait time 0,10 10000,0 s 0,50 717 Wait time before the firstreset is executed.P3.10.4 Trial time 0,00 10000,0 s 60,00 718When the trial time haselapsed, and the fault is stillactive, the drive will trip tofault.P3.10.5 Number of trials 1 10 4 759 NOTE! Total number of trials(irrespective of fault type)P3.10.6 Autoreset:Undervoltage 0 1 1 720Autoreset permitted?0 = No1 = YesP3.10.7 Autoreset:Overvoltage 0 1 1 721Autoreset permitted?0 = No1 = YesP3.10.8 Autoreset:Overcurrent 0 1 1 722Autoreset permitted?0 = No1 = YesP3.10.9 Autoreset: AI low 0 1 1 723Autoreset permitted?0 = No1 = YesP3.10.10 Autoreset: Unitovertemperature 0 1 1 724Autoreset permitted?0 = No1 = YesP3.10.11 Autoreset: Motorovertemperature 0 1 1 725Autoreset permitted?0 = No1 = YesP3.10.12 Autoreset:External fault 0 1 0 726Autoreset permitted?0 = No1 = YesP3.10.13 Autoreset:Underload fault 0 1 0 738Autoreset permitted?0 = No1 = YesP3.10.14 PID Supervision No Yes No 15538 Include fault in the automaticreset function.