Vacon HVAC Application vacon • 8024-hour support +358 (0)201 212 575 • Email: vacon@vacon.com33.6.15 Group 3.13: PID-controller 23.6.15.1 Basic settingsFor more detailed information, see Chapter 3.6.14.3.6.15.2 SetpointsTable 64:Index Parameter Min Max Unit Default ID DescriptionP3.13.1.1 Enable PID 0 1 0 1630 0 = Disabled1 = EnabledP3.13.1.2 Output in Stop 0.0 100.0 % 0.0 1100The output value of the PIDcontroller in % of itsmaximum output value whileit is stopped from digitalinput.P3.13.1.3 PID gain 0.00 1000.00 % 100.00 1631P3.13.1.4 PID integration time 0.00 600.00 s 1.00 1632P3.13.1.5 PID derivation time 0.00 100.00 s 0.00 1633P3.13.1.6 Process unit selection 1 38 1 1635P3.13.1.7 Process unit min Varies Varies Varies 0 1664P3.13.1.8 Process unit max Varies Varies Varies 100 1665P3.13.1.9 Process unit decimals 0 4 2 1666P3.13.1.10 Error inversion 0 1 0 1636P3.13.1.11 Dead band hysteresis Varies Varies Varies 0.0 1637P3.13.1.12 Dead band delay 0.00 320.00 s 0.00 1638Table 65:Index Parameter Min Max Unit Default ID DescriptionP3.13.2.1 Keypad setpoint 1 0.00 100.00 Varies 0.00 1640P3.13.2.2 Keypad setpoint 2 0.00 100.00 Varies 0.00 1641P3.13.2.3 Setpoint ramp time 0.00 300.00 s 0.00 1642P3.13.2.4 Setpoint source 1selection 0 16 1 1643P3.13.2.5 Setpoint 1 minimum -200.00 200.00 % 0.00 1644 Minimum value at analoguesignal minimum.P3.13.2.6 Setpoint 1 maximum -200.00 200.00 % 100.00 1645 Maximum value at analoguesignal maximum.P3.13.2.7 Setpoint source 2selection 0 16 0 1646 See P3.13.2.4.P3.13.2.8 Setpoint 2 minimum -200.00 200.00 % 0.00 1647 Minimum value at analoguesignal minimum.P3.13.2.9 Setpoint 2 maximum -200.00 200.00 % 100.00 1648 Maximum value at analoguesignal maximum.