3vacon • 83 Vacon HVAC ApplicationTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2053.6.17 Group 3.16: Fire modeDrive ignores all commands from keypad, fieldbuses and PC tool and runs at preset frequencywhen activated. If activated, alarm sign is shown on the keypad and warranty is void. In orderto enable the function, you need to set a password in the description field for parameter FireMode password. Please note the NC (normally closed) type of this input!NOTE! THE WARRANTY IS VOID IF THIS FUNCTION IS ACTIVATED! There is also a differentpassword for test mode to be used for testing the Fire Mode without the warranty becomingvoid.Table 69: Fire mode parametersIndex Parameter Min Max Unit Default ID DescriptionP3.16.1 Fire Mode password 0 9999 0 1599 1001 = Enabled1234 = Test modeP3.16.2 Fire Mode Activ.Open DigIN Slot0.2 1596 FALSE = Fire Mode activeTRUE = InactiveP3.16.3 Fire Mode Activ.Close DigIN Slot0.1 1619 FALSE = InactiveTRUE = Fire Mode ActiveP3.16.4 Fire Mode frequency 8.00 P3.3.2 Hz 0.00 1598 Frequency used when FireMode is activated.P3.16.5 Fire Mode frequencysource 0 8 0 1617Selection of reference sourcewhen Fire Mode is active.This enables selection of e.g.AI1 or PID controller asreference source also whileoperating in Fire Mode.0 = Fire Mode frequency1 = Preset speeds2 = Keypad3 = Fieldbus4 = AI15 = AI26 = AI1 + AI27 = PID18 = Motor potentiometerP3.16.6 Fire Mode reverse DigIN Slot0.1 1618Reverse command ofrotation direction whilerunning in Fire Mode. Thisfunction has no effect innormal operation.FALSE = ForwardTRUE = ReverseP3.16.7 Fire Mode presetfrequency 1 0 50 10 15535 Preset frequency for FireModeP3.16.8 Fire Mode presetfrequency 2 0 50 20 15536 See above.P3.16.9 Fire Mode presetfrequency 3 0 50 30 15537 See above.M3.16.10 Fire Mode status 0 3 0 1597Monitoring value (see alsoTable 31)0 = Disabled1 = Enabled2 = Activated (Enabled + DIOpen)3 = Test Mode