Brake Chopper Application – Parameter lists vacon • 1124-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com3.7 Protections (Menu G2 Æ G2.6)Code Parameter Default Min Max Unit ID NoteP2.6.1 PT100 Numbers 0 0 3 739Number of PT100inputs in use at OPT-B8 option board.Visible only when theoption board hasbeen installedP2.6.2 PT100 Alarm Lim 110 -30 200 °C 1347Select thetemperature for PT100sensor above whichPT100 alarm isgenerated in the drive.P2.6.3 PT100 Fault Lim 120PT100Alarmlimit(P2.6.2)300 °C 1348Select thetemperature for PT100sensor above whichPT100 fault isgenerated in the driveP2.6.4 Thermistor 1 0 2 1351Response tothermistorovertemperature.0=No Action,1=Warning,2=FaultP2.6.5 External Fault 2 0 2 701Response to Externalfault.0=No action,1=Warning,2=FaultTable 3-9. Protections G2.63.8 Keypad control (Control keypad: Menu M3)Code Parameter Default Min Max Unit ID DescriptionP3.1 Control place 0 0 1 125 0=I/O terminal (default)1=FieldbusTable 3-10. Keypad control parameters M33.9 System menu (Control keypad: Menu M6)For parameters and functions related to the general use of the frequency converter, such asapplication and language selection, customised parameter sets or information about the hardwareand software, see Chapter 7.3.6 in the Vacon NX User's Manual.3.10 Expander boards (Control keypad: Menu M7)The M7 menu shows the expander and option boards attached to the control board and board-related information. For more information, see Chapter 7.3.7 in the Vacon NX User's Manual.