Description of parameters vacon • 1324-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com4.2 Input signals4.2.1 Digital Inputs2.2.1.1 Fault Reset (ID1208)Input selection for Fault Resetting. The transition from Off to On will reset the fault if thecause of the fault has been removed.0 = Not used1 = DIN12 = DIN23 = DIN34 = DIN45 = DIN56 = DIN62.2.1.2 External fault (ID1214)This parameter defines if the BCU monitors status of the External fault input. WithExternal fault it is possible to trig a fault 51. Response to the fault can be defined withthe parameter P2.6.5.See parameter P2.2.1.1 for the list of values.2.2.1.3 Run Enable (ID1212)This parameter is used for choosing the input for external Run Enable signal. If theoption “0 = Not used” have been selected the Run Enable signal is always on.See parameter P2.2.1.1 for the list of values.2.2.1.4 KLIXON Input (ID1209)This parameter is used for choosing the input for KLIXON type temperature sensor. Thefunction of this input is Normally Closed so the fault “60 = KLIXON” is generated whenthe input goes low.See parameter P2.2.1.1 for the list of values.