110 • vacon CONTROL KEYPADTel. +358 (0)201 2121 • Fax +358 (0)201 212 20577.3.7 Expander board menu (M7)TheExpander board menu makes it possible for the user 1) to see what expander boards are connected tothe control board and 2) to reach and edit the parameters associated with the expander board.Enter the following menu level (G#) with theMenu button right. At this level, you can browse through slots(see page 69) A to E with theBrowser buttons to see what expander boards are connected. On thelowermost line of the display you also see the number of parameters associated with the board. You canview and edit the parameter values in the same way as described in chapter 7.3.2. See Table 7-12 andFigure 7-27.Expander board parametersCode Parameter Min Max Default Cust SelectionsP7.1.1.1 AI1 mode 1 5 31=0…20 mA2=4…20 mA3=0…10 V4=2…10 V5=–10…+10 VP7.1.1.2 AI2 mode 1 5 1 See P7.1.1.1P7.1.1.3 AO1 mode 1 4 11=0…20 mA2=4…20 mA3=0…10 V4=2…10 VTable 7-12. Expander board parameters (board OPTA1)Figure 7-27. Expander board information menu7.4 Further keypad functionsThe Vacon NX control keypad embodies additional application-related functions. See Vacon NX ApplicationPackage for more information.G1G5READY READYG1G2READYREADYenterP1P4R EA DYI/OtermG1G2R EA DYI/OtermV1V2READYR EA DYI/OtermD:NXOPTC2C:NXOPTC1Expander boards ParametersSlave address126Slave address126Baud rateAutoMonitorC H AN GE VAL UEC ON FIR M CHANGE