TECHNICAL DATA vacon • 2324-hour support +358 (0)201 212 575 • Email: vacon@vacon.com 44.2.3 Vacon NX_6 – Mains voltage 525—690 VHigh overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 minFollowing continuous operation at rated output current, 150 % rated output current (IH)for 1 min, followed by a period of load current less than rated current, and of suchduration that the r.m.s output current, over the duty cycle, does not exceed ratedoutput current (IH)Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 minFollowing continuous operation at rated output current, 110% rated output current (IL)for 1 min, followed by a period of load current less than rated current, and of suchduration that the r.m.s output current, over the duty cycle, does not exceed ratedoutput current (IL)All sizes are available as IP21/NEMA1 Sizes FR4 to FR10 are additionally available as IP54/NEMA12.FR12 is available only as NXP.Mains voltage 525-690 V, 50/60 Hz, 3~FrequencyconvertertypeLoadability Motor shaft powerFrameDimensions andweightWxHxD/kgLow High 690V supply 575V supplyRatedcontinuouscurrent IL(A)10%overloadcurrent(A)Ratedcontinuouscurrent IH(A)50%overloadcurrent(A)MaxcurrentIS10%overload40°CP(kW)50%overload50°CP(kW)10%overload40°CP(hp)50%overload50°CP(hp)NX_ 0004 6 4.5 5.0 3.2 4.8 6.4 3 2.2 3.0 2.0 FR6 195x519x237/18,5NX_ 0005 6 5.5 6.1 4.5 6.8 9.0 4 3 3.0 3.0 FR6 195x519x237/18,5NX_ 0007 6 7.5 8.3 5.5 8.3 11.0 5.5 4 5.0 3.0 FR6 195x519x237/18,5NX_ 0010 6 10 11.0 7.5 11.3 15.0 7.5 5.5 7.5 5.0 FR6 195x519x237/18,5NX_ 0013 6 13.5 14.9 10 15.0 20.0 11 7.5 10 7.5 FR6 195x519x237/18,5NX_ 0018 6 18 19.8 13.5 20.3 27 15 11 15 10 FR6 195x519x237/18,5NX_ 0022 6 22 24.2 18 27.0 36 18.5 15 20 15 FR6 195x519x237/18,5NX_ 0027 6 27 29.7 22 33.0 44 22 18.5 25 20 FR6 195x519x237/18,5NX_ 0034 6 34 37 27 41 54 30 22 30 25 FR6 195x519x237/18,5NX_ 0041 6 41 45 34 51 68 37.5 30 40 30 FR7 237x591x257/35NX_ 0052 6 52 57 41 62 82 45 37.5 50 40 FR7 237x591x257/35NX_ 0062 6 62 68 52 78 104 55 45 60 50 FR8 291x758x344/58NX_ 0080 6 80 88 62 93 124 75 55 75 60 FR8 291x758x344/58NX_ 0100 6 100 110 80 120 160 90 75 100 75 FR8 291x758x344/58NX_ 0125 6 125 138 100 150 200 110 90 125 100 FR9 480x1150x362/146NX_ 0144 6 144 158 125 188 213 132 110 150 125 FR9 480x1150x362/146NX_ 0170 6 170 187 144 216 245 160 132 150 150 FR9 480x1150x362/146NX_ 0208 6 208 229 170 255 289 200 160 200 150 FR9 480x1150x362/146NX_ 0261 6 261 287 208 312 375 250 200 250 200 FR10 595x2018x602/340NX_ 0325 6 325 358 261 392 470 315 250 300 250 FR10 595x2018x602/340NX_ 0385 6 385 424 325 488 585 355 315 400 300 FR10 595x2018x602/340NX_ 0416 6 416 458 325 488 585 400 315 450 300 FR10 595x2018x602/340NX_ 0460 6 460 506 385 578 693 450 355 450 400 FR11 794x2018x602/400NX_ 0502 6 502 552 460 690 828 500 450 500 450 FR11 794x2018x602/400NX_ 0590 6 590 649 502 753 904 560 500 600 500 FR11 794x2018x602/470NXP 0650 6 650 715 590 885 1062 630 560 650 600 FR12 1210x2017x602/600NXP 0750 6 750 825 650 975 1170 710 630 800 650 FR12 1210x2017x602/600NXP 0820 6 820 902 650 975 1170 800 630 800 650 FR12 1210x2017x602/600Table 4-3. Power ratings and dimensions of Vacon NX_, supply voltage 525—690V.Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal toor less than the factory default.Note: The rated currents for FR10 to FR12 are valid at an ambient temperature of 40°C (except for 0416 6, 0590 6 and0820 6: rated currents valid at an ambient temperature of 35°C).