48 • vacon CABLING AND CONNECTIONSTel. +358 (0)201 2121 • Fax +358 (0)201 212 20566.1.1.6 Cable and fuse sizes, NX_5, FR10 to FR11The table below shows typical cable sizes and types that can be used with the converter. The final selectionshould be made according to local regulations, cable installation conditions and cable specification.Frame Type IL[A]Fuse In[A]Mains and motorcable1) [mm2 ]No. ofsupplycablesNo. of motorcablesFR10NX0385 5 385 400 (3 pcs) Cu: 2*(3*120+70)Al: 2*(3*185Al+57Cu)Even/Odd Even/OddNX0460 5 460 500 (3 pcs) Cu: 2*(3*150+70)Al: 2*(3*240Al+72Cu)Even/Odd Even/OddNX0520 5 520 630 (3 pcs) Cu: 2*(3*185+95)Al: 2*(3*300Al+88Cu)Even/Odd Even/OddFR11NX0590 5 590 315 (6 pcs) Cu: 2*(3*240+120)Al: 4*(3*120Al+41Cu)Even Even/OddNX0650 5 650 400 (6 pcs) Cu: 4*(3*95+50)Al: 4*(3*150Al+41Cu)Even Even/OddNX0730 5 730 400 (6 pcs) Cu: 4*(3*120+70)Al: 4*(3*185Al+57Cu)Even Even/OddNX0820 5 820 500 (6 pcs) Cu: 4*(3*150+70)Al: 4*(3*185Al+57Cu)Even EvenNX0920 5 920 500 (6 pcs) Cu: 4*(3*150+70)Al: 4*(3*240Al+72Cu)Even EvenNX1030 5 1030 630 (6 pcs) Cu: 4*(3*185+95)Al: 4*(3*300Al+88Cu)Even EvenTable 6-4. Cable and fuse sizes for Vacon NX_5 (FR10 to FR11)1)based on correction factor 0.76.1.1.7 Cable and fuse sizes, NX_6, FR10 to FR11The table below shows typical cable sizes and types that can be used with the converter. The final selectionshould be made according to local regulations, cable installation conditions and cable specification.Frame Type IL[A]Fuse In[A]Mains and motorcable1)[mm2 ]No ofsupplycablesNo ofmotorcablesFR10NX0261 6 261 315 (3 pcs) Cu: 3*185+95Al: 2*(3*95Al+29Cu)Even/Odd Even/OddNX0325 6 325 400 (3 pcs) Cu: 2*(3*95+50)Al: 2*(3*150Al+41Cu)Even/Odd Even/OddNX0385 6 385 400 (3 pcs) Cu: 2*(3*120+70)Al: 2*(3*185Al+57Cu)Even/Odd Even/OddNX0416 6 416 500 (3 pcs) Cu: 2*(3*150+70)Al: 2*(3*185Al+57Cu)Even/Odd Even/OddFR11NX0460 6 460 500 (3 pcs) Cu: 2*(3*150+70)Al: 2*(3*240Al+72Cu)Even/Odd Even/OddNX0502 6 502 630 (3 pcs) Cu: 2*(3*185+95)Al: 2*(3*300Al+88 Cu)Even/Odd Even/OddNX0590 6 590 315 (6 pcs) Cu: 2*(3*240+120)Al: 4*(3*120Al+41Cu)Even Even/OddNX0650 6 650 400 (6 pcs) Cu: 4*(3*95+50)Al: 4*(3*150Al+41Cu)Even EvenNX0750 6 750 400 (6 pcs) Cu: 4*(3*120+70)Al: 4*(3*150Al+41Cu)Even EvenNX0820 6 820 500 (6 pcs) Cu: 4*(3*150+70)Al: 4*(3*185Al+57Cu)Even EvenTable 6-5. Cable and fuse sizes for Vacon NX_6 (FR10 to FR11)1)based on correction factor 0.7