78 Process Image WAGO-I/O-SYSTEM 750750-464 2/4 AI RTD configurableManualVersion 1.0.17.3.6 Ni120 (Minco)With the setting "Ni120 (Minco)", the I/O module converts the resistancemeasured values of Ni120 sensors (Minco) and outputs them as temperaturevalues.The temperature values are displayed at a resolution of 1 digit per 0.1 °C in oneword (16-bit). Temperature values below 0 °C are represented in two'scomplement binary. As a result, 0 °C corresponds to the numeric value 0x0000and 100 °C to the numeric value 0x03E8 (dec. 1000).The possible numeric range corresponds to the defined temperature range of-80 °C to +260 °C for Ni120 sensors (Minco).Table 64: Process image for 750-464, Ni120 setting (Minco)Temperature°CResistanceΩNumeric value 1) Statusbytehex.LEDerrorAI 1, 2Binary Hex. Dec.--- < 9.00 '1111.1100.1110.0000' 0xFCE0 -800 0x51 onShort circuit 2)< -80.0 66.60 '1111.1100.1110.0000' 0xFCE0 -800 0x41 onUnderrange 3)-80.0 66.60 '1111.1100.1110.0000' 0xFCE0 -800 0x00 off-50.0 86.16 '1111.1110.0000.1100' 0xFE0C -500 0x00 off0.0 120.00 '0000.0000.0000.0000' 0x0000 0 0x00 off50.0 157.75 '0000.0001.1111.0100' 0x01F4 500 0x00 off100.0 200.64 '0000.0011.1110.1000' 0x03E8 1000 0x00 off150.0 248.95 '0000.0101.1101.1100' 0x05DC 1500 0x00 off200.0 303.45 '0000.0111.1101.0000' 0x07D0 2000 0x00 off250.0 366.53 '0000.1001.1100.0100' 0x09C4 2500 0x00 off260.0 380.31 '0000.1010.0010.1000' 0x0A28 2600 0x00 off> 260.0 > 380.31 '0000.1010.0010.1000' 0x0A28 2600 0x42 onOverrange 3)--- > 5500.00 '0000.1010.0010.1000' 0x0A28 2600 0x62 onWire break 2)1) Temperature values below 0 °C are represented in two's complement binary.2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of anError")3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")