WAGO-I/O-SYSTEM 750 Process Image 87750-464 2/4 AI RTD configurableManualVersion 1.0.17.4.4 Pt1000 (acc. IEC 751)With the setting "Pt1000 (acc. IEC 751)" and activated Siemens format, the I/Omodule converts the resistance measured values of Pt1000 sensors (acc. IEC 751)and outputs them as temperature values.The temperature values are displayed at a resolution of 1 digit per 0.5 °C.The status information is depicted in bit 0 to bit 2 and the digitalized measuredvalue in bit 3 to bit 15.Table 73: Process image for 750-464, Pt1000 setting (acc. IEC 751)Temperature°CResistanceΩNumeric value 1) with status information 4) Statusbytehex.LEDerrorAI 1, 2Binary XFÜ Hex. Dec.--- < 9.00 '1111.0011.1000.0 011' 0xF383 -3197 0x51 onShort circuit 2)< -200.0 < 185.20 '1111.0011.1000.0 001' 0xF381 -3199 0x41 onUnderrange 3)-200.0 185.20 '1111.0011.1000.0 000' 0xF380 -3200 0x00 off-100.0 602.56 '1111.1001.1100.0 000' 0xF9C0 -1600 0x00 off0.0 1000.00 '0000.0000.0000.0 000' 0x0000 0 0x00 off100.0 1385.06 '0000.0011.1110.1 000' 0x0640 1600 0x00 off200.0 1758.56 '0000.0111.1101.0 000' 0x0C80 3200 0x00 off500.0 2809.78 '0001.1111.0100.0 000' 0x1F40 8000 0x00 off750.0 3606.38 '0010.1110.1110.0 000' 0x2EE0 12000 0x00 off800.0 3757.04 '0011.0010.0000.0 000' 0x3200 12800 0x00 off850.0 3904.81 '0011.0101.0010.0 000' 0x3520 13600 0x00 off> 850.0 > 3904.81 '0011.0101.0010.0 001' 0x3521 13601 0x42 onOverrange 3)--- > 5500.00 '0011.0101.0010.0 011' 0x3523 13603 0x62 onWire break 2)1) Temperature values below 0 °C are represented in two's complement binary.2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of anError")3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")4) Status information: X: Not used, F: Short circuit, wire break, Ü: Overrange