WAGO-I/O-SYSTEM 750 Function Description 47750-632 Proportional Valve ModuleManualVersion 1.3.0, valid from FW/HW-Version 01/01Table 31: Approach End Stop ValueNo. Event Description/Behavior1 Set SPL_EN to “0” “JOG mode” is activated.Present current level is maintained.2 Set JOG_POS to “1”Set JOG_POS to “0”Present current level is increased.Present current level is maintained.3 Set JOG_POS to “1” Present current level is increased.4 Set DI to “1”. Rising ramp stops. Actual value drops until theend stop value is reached. The actual value isthen frozen.5 Set DI to “0”. Present current level is maintained.6 Set JOG_POS to “0” Present current level is maintained.7 Set JOG_NEG to “1”Set JOG_NEG to “0”Present current level is reducedPresent current level is maintained.8 Set JOG_POS to “1” Present current level is increased.9 Set DI to “1”. Rising ramp stops. Actual value drops until theend stop value is reached. The actual value isthen frozen.10 Set JOG_POS to “0” Present current level is maintained.11 Set JOG_POS to “1”Set JOG_POS to “0”Present current level is increased(even if the DI is still active).Present current level is maintained.12 Set DI to “0”. Present current level is maintained.