86 Commissioning WAGO-I/O-SYSTEM 750750-632 Proportional Valve ModuleManualVersion 1.3.0, valid from FW/HW-Version 01/019.1.1.3.2 “Module Parameters” Menu ItemVarious I/O module parameters can be set using this menu item:Figure 46: “Module Parameters” Menu ItemTable 57: “Module parameters” menu itemOption DescriptionTipp ModeTIP Time The time period for TIP mode can be defined.Activate TIP mode is activated. TIP mode is deactivated.Target WindowCurrent Value This value is the tolerance threshold [in percent] for the setpoint valueentered (see “Operation” menu item).Example: If the setpoint value = 50 % and the setting = 1 %, the targetposition is reached (bit “On Target” = “1”), if the actual value is between49 % and 51 %.K-Bus Failure *Enable manualoperation for: Manual mode is permitted for the respective valve. Manual mode is not permitted for the respective valve.Substitute Value ConfigurationShow last value fromprocess image.The final value contained in the process image serves as the substitutevalue.Show substitute valuefor current.The value defined in the “Substitute value, current” input field serves asthe substitute value.* Function supported in software version 03 or higher.