202 I/O Modules WAGO-I/O-SYSTEM 750758-874/000-110 WAGO-I/O-IPC-C6ManualVersion 2.3.0The above SSI Transmitter Interface modules have a total of 4 bytes of user datain the Input Process Image, which has 2 words mapped into the image.Word alignment is applied.Table 99: SSI Transmitter Interface ModulesInput Process ImageByte DestinationOffset High Byte Low Byte Description0 D1 D01 D3 D2 Data bytes17.2.5.7 Incremental Encoder Interface Modules750-631/000-004, -010, -011The above Incremental Encoder Interface modules have 5 bytes of input data and3 bytes of output data. The following tables illustrate the Input and Output ProcessImage, which have 4 words into each image. Word alignment is applied.Table 100: Incremental Encoder Interface Modules 750-631/000-004, --010, -011Input Process ImageByte DestinationOffset High Byte Low Byte Description0 - S not used Status byte1 D1 D0 Counter word2 - - not used3 D4 D3 Latch wordOutput Process ImageByte DestinationOffset High Byte Low Byte Description0 - C not used Control byte1 D1 D0 Counter setting word2 - - not used3 - - not used750-634The above Incremental Encoder Interface module has 5 bytes of input data (6bytes in cycle duration measurement mode) and 3 bytes of output data. Thefollowing tables illustrate the Input and Output Process Image, which has 4 wordsmapped into each image. Word alignment is applied.