WAGO-I/O-SYSTEM 750 I/O Modules 209758-874/000-110 WAGO-I/O-IPC-C6ManualVersion 2.3.017.2.5.15 Vibration Velocity/Bearing Condition Monitoring VIB I/O750-645The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of 12bytes of user data in both the Input and Output Process Image (8 bytes of moduledata and 4 bytes of control/status). The following table illustrates the Input andOutput Process Image, which have 8 words mapped into each image.Word alignment is applied.Table 111: Vibration Velocity/Bearing Condition Monitoring VIB I/O 750-645Input and Output Process ImageByte DestinationOffset High Byte Low Byte Description0 - C0/S0 not usedControl/status byte(log. Channel 1,Sensor input 1)1 D1 D0 Data bytes(log. Channel 1, Sensor input 1)2 - C1/S1 not usedControl/status byte(log. Channel 2,Sensor input 2)3 D3 D2 Data bytes(log. Channel 2, Sensor input 2)4 - C2/S2 not usedControl/status byte(log. Channel 3,Sensor input 1)5 D5 D4 Data bytes(log. Channel 3, Sensor input 3)6 - C3/S3 not usedControl/status byte(log. Channel 4,Sensor input 2)7 D7 D6 Data bytes(log. Channel 4, Sensor input 2)Pos: 60.17 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - 753-646 KNX/EIB (750-830, -842, -849) @ 5\mod_1253540550198_21.doc @ 41890 @ 4 @ 117.2.5.16 KNX/EIB/TP1 Module753-646The KNX/TP1 module appears in router and device mode with a total of 24-byteuser data within the input and output area of the process image, 20 data bytes and2 control/status bytes. Even though the additional bytes S1 or C1 are transferredas data bytes, they are used as extended status and control bytes. The opcode isused for the read/write command of data and the triggering of specific functionsof the KNX/EIB/TP1 module. Word-alignment is used to assign 12 words in theprocess image. Access to the process image is not possible in router mode.Telegrams can only be tunneled.In device mode, access to the KNX data can only be performed via specialfunction blocks of the IEC application. Configuration using the ETS engineeringtool software is required for KNX.