212 I/O Modules WAGO-I/O-SYSTEM 750758-874/000-110 WAGO-I/O-IPC-C6ManualVersion 2.3.017.2.6 System Modules17.2.6.1 System Modules with Diagnostics750-610, -611The modules provide 2 bits of diagnostics in the Input Process Image formonitoring of the internal power supply.Table 114: System Modules with Diagnostics 750-610, -611Input Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Diagnosticbit S 2FuseDiagnosticbit S 1FusePos: 60.19 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - MODBUS TCP Teil 3 Binäre Platzhalterklemmen - letzte Klemme @ 8\mod_1279182270905_21.doc @ 60020 @ 4 @ 117.2.6.2 Binary Space Module750-622The Binary Space Modules behave alternatively like 2 channel digital inputmodules or output modules and seize depending upon the selected settings 1, 2, 3or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are occupied then either inthe process input or the process output image.Table 115: Binary Space Module 750-622 (with behavior like 2 channel digital input)Input and Output Process ImageBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0(Data bitDI 8)(Data bitDI 7)(Data bitDI 6)(Data bitDI 5)(Data bitDI 4)(Data bitDI 3)Data bitDI 2Data bitDI 1Pos: 61 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1