GPi 3200 / 4300 Operationwc_tx001239gb.fm 332.16 Starting the Generator (Manual Start Models)StartingprocedureFollow the procedure below to start the machine.1. Turn the engine switch (h) to the CHOKE position (or the RUN position if theengine is warm or the ambient temperature is high).2. Pull the recoil starter (f) slowly until you feel resistance.3. After you feel resistance, return the recoil starter to its original position and pullquickly. The engine will start.4. If you started the engine with the engine switch in the CHOKE position, allow theengine to run for 20–30 seconds and then turn the engine switch to the RUNposition.5. Use the LED changeover switch (n) to switch to display voltage on the LCD. Areading of 120V indicates that the generator is operating properly.Troubleshooting If the engine does not start after several attempts, repeat the starting procedurewith the engine switch turned to the RUN position. If the engine still does not start,refer to the Troubleshooting chapter.CAUTIONPersonal injury or machine damage hazards. Starting the generator with equipmentattached can damage the generator or the equipment. Unexpected equipmentstart-up can cause personal injury.f Disconnect all equpment from the generator before starting it.wc_gr006840hnf