54.3. SpecificationsUnless otherwise noted, specifications are warranted over the ambient temperature range of 0 to 40 ºC.Notes:1. Minimum voltage is guaranteed at greater than 1% of the rated output voltage.2. Minimum current is guaranteed at greater than 1% of the rated output current.3. Measured with 20 MHz bandwidth and excluding line frequency ripple (see application note AN024 for measurement details, these measurements taken at full ratedoutput voltage and full power.4. Line frequency ripple measured with 20 MHz bandwidth (see application note AN024 for measurement details, these measurements taken at full rated outputvoltage and full power.5. Time for output voltage to recover within 0.5% of its rated output for a load change from 10 to 90% of its rated output current.6. Voltage set point from 10% to 100% of rated output7. Add this to the output response time to obtain the total programming time8. Time to provide data back to the controller using LAN interface (does not include A/D conversion time)PLS6003033 PLS6005020 PLS60010010 PLS6002005 PLS6004002.5DC Output Ratings (1)Voltage 30 V 50 V 100 V 200 V 400 VCurrent 33 A 20 A 10 A 5 A 2.5 APower 600 W 600 W 600 W 600 W 600 WOutput Ripple & Noise CV p-p 3 60 mV 100 mV 100 mV 100 mV 200 mVCV rms4 20 mV 100 mV 150 mV 150 mV 50 mVLoad Regulation(change from 10%-90% load)Voltage 15 mV 25 mV 50 mV 100 mV 200 mVCurrent 15 mV 15 mV 15 mA 15 mA 15 mALine Regulation(change from 100-132 VAC input or180-260 VAC input) (5)Voltage 15 mV 25 mV 50 mV 100 mV 200 mVCurrent 15 mV 15 mV 15 mA 15 mA 15 mAProgramming Accurancy (1,2) Voltage 0.1%+ 15 mV 25 mV 50 mV 100 mV 200 mVCurrent 0.1%+ 66 mA 40 mA 20 mA 10 mA 5 mAMeasurement Accuracy Voltage 0.1%+ 15 mV 25 mV 50 mV 100 mV 200 mVCurrent 0.1%+ 60 mA 40 mA 15 mA 10 mA 5 mATransient Recovery Time (5) Time ≤1 ms ≤1 ms ≤1 ms ≤1 ms ≤1 msSupplemental Characteristics (supplemental characteristics are not warranted but are descriptions of typical performance determindeither by design or type testing)Output Response Time(settle to within ±1% of the ratedoutput, with resistive load)Up, Full Load 0.08 s 0.08 s 0.08 s 0.08 s 0.08 sDown, Full Load 0.08 s 0.08 s 0.08 s 0.08 s 0.08 sDown, No Load 0.5 s 0.5 s 0.5 s 0.5 s 0.5 sCommand Response Time(7) 50 ms 50 ms 50 ms 50 ms 50 ms 50 msData Readback Transfer Time(8) 5 ms 5 ms 5 ms 5 ms 5 ms 5 msRemote Sense Compensation Volts/Load Lead 1 V 1 V 2 V 4 V 4 VOver-voltage Protection Range 0.5-33 V 0.5-55 V 0.5-110 V 0.5-220 V 0.5-440 VAccuracy 0.3 V 0.5 V 1 V 2 V 4 VOutput Ripple & Noise(3) CC rms 7 mA 5 mA 5 mA 5 mA 10 mAProgramming ResolutionMeasurement ResolutionVoltage 0.05%+ 10 mV 25 mV 50 mV 100 mV 200 mVCurrent 0.05%+ 20 mA 20 mA 10 mA 5 mA 2.5 mAFront Panel Display Accuracy Voltage 0.1%+ 10 mV 25 mV 50 mV 100 mV 200 mVCurrent 0.1%+ 33 mA 20 mA 10 mA 5 mA 2.5 mA