Examples:• For inverse output of “8: During baseblock”, set 108.• For inverse output of “4A: During KEB” set 14A.n H2-06: Watt Hour Output Unit SelectionWhen one of the multi-function terminals is set to output the number of watt hours (H2-01, H2-02, or H2-03 = 39), parameterH2-06 determines the units for the output signal.This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the frequency thatpulses are issued to keep track of the kWh for the drive.No. Parameter Name Setting Range DefaultH2-06 Watt Hour Output Unit Selection0: 0.1 kWh units1: 1 kWh units2: 10 kWh units3: 100 kWh units4: 1000 kWh units0Note: 1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.0.2 sH2-06(Pulse Output Unit)H2-01 to 03(Multi-function Output)Integral Power (every 100 ms)OFF OFFONFigure 1.74 Watt Hour Output Exampleu H3: Multi-Function Analog InputsThe drive is equipped with three multi-function analog input terminals: A1, A2, and A3. Refer to Multi-Function AnalogInput Terminal Settings on page 118 for a listing of the functions that can be set to these terminals.n H3-01: Terminal A1 Signal Level SelectionSelects the input signal level for analog input A1.No. Name Setting Range DefaultH3-01 Terminal A1 Signal Level Selection 0 to 1 0Setting 0: 0 to 10 VdcThe input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and biassettings will be read as 0%.Setting 1: -10 to 10 VdcThe input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then themotor will rotate in reverse.n H3-02: Terminal A1 Function SelectionSelects the input signal level for analog input A1. Refer to Multi-Function Analog Input Terminal Settings on page 118 forinstructions on adjusting the signal level.No. Name Setting Range DefaultH3-02 Terminal A1 Function Selection 0n H3-03, H3-04: Terminal A1 Gain and Bias SettingsParameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).1.7 H: Terminal FunctionsYASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual 1151 Parameter Details