U1-02: output frequencyU1-05: motor speedU1-16: output frequency after softstarter (accel/decel ramp generator)d1-01 to d1-17: frequency references2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.n o1-04: V/f Pattern Display UnitNote: PM motor control modes are not available in A1000 HHP drive models.Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06, E1-09,E1-11, and E2-04. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E3-11. Enabled only in vectorcontrol modes (CLV, AOLV/PM, CLV/PM).No. Name Setting Range Defaulto1-04 V/f Pattern Display Unit 0, 1 0Setting 0: HertzSetting 1: r/minNote: For motor 2, o1-04 can only be set to 0 for Hertz.n o1-10: User-Set Display Units Maximum ValueDetermines the display value that is equal to the maximum output frequency.No. Name Setting Range Defaulto1-10 User-Set Display Units Maximum Value 1 to 60000 Determined byo1-03n o1-11: User-Set Display Units Decimal DisplayDetermines how many decimal points should be used to set and display the frequency reference.No. Name Setting Range Defaulto1-11 User-Set Display Units Decimal Display 0 to 3 Determined byo1-03Setting 0: No Decimal PointSetting 1: One Decimal PointSetting 2: Two Decimal PointsSetting 3: Three Decimal Pointsu o2: Digital Operator Keypad FunctionsThese parameters determine the functions assigned to the operator keys.n o2-01: LO/RE (LOCAL/REMOTE) Key Function SelectionDetermines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.No. Name Setting Range Defaulto2-01 LO/RE Key Function Selection 0, 1 1Setting 0: DisabledThe LO/RE key is disabled.Setting 1: EnabledThe LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL isselected, the LED indicator on the LO/RE key will light up.WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching fromLOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connectionsthoroughly before making any setting changes to o2-01 and b1-07. Table 1.43 lists the setting combinations for o2-01 and b1-07.1.10 o: Operator Related Settings162 YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual