9 Web Interface48 YASKAWA ELECTRIC SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual Email Alerts PageThe Email Alerts page allows the user to configure four Email Fault/Alarm conditions. When the condition is true, oneemail will be sent to the provided email address. Another email will not be sent until the condition becomes false andthen true again. A 30-second timer prevents emails from being sent when conditions reoccur immediately after beingremoved. The timer helps limit the amount of emails sent regarding the same intermittent condition and helps to reducenetwork traffic by reducing emails about reoccurring errors.Figure 23Figure 24 Email Alerts Page View Procedure: Conditional Email Set-up1. Click the “Enable” check box to enable the alert.2. Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value. Setthe conditions to send alerts from the “Condition” drop-down selection. If choosing only one condition and no ORor AND are needed, set the “OR/AND” drop-down selection to “---”.3. Enter the email address where the alert will be sent.4. Enter the message that will appear in the email contents.5. Enter the email subject.Clicking “Save Email Settings” will save the entered information into the option.