4.5 Test Run174 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)■ Password Settings: A1-04, A1-05The user can set a password to the drive to restrict access. The password is selectedvia parameter A1-05. The selected password must be entered in parameter A1-04to unlock parameter access (i.e. parameter setting A1-04 must match the valueprogrammed into A1-05). The following parameters cannot be viewed or editeduntil the value programmed into A1-04 correctly matches the value as programmedin parameter A1-05: A1-01, A1-02, A1-03, A1-06 and A2-01 through A2-33.Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04and simultaneously depress the key and the key.◆ Jog Operation: FJOG/RJOGImplement Forward and Reverse Jog functions using the multi-function inputterminals (S1 to S7). Separate frequency settings for forward jog (FJOG) andreverse jog (RJOG) cannot be set. The jog frequency reference for both forwardand reverse jog commands is set in parameter d1-17.No. ParameterName Description SettingRange Default PageA1-01AccessLevelSelectionSelects which parameters are accessible via the digitaloperator.0: Operation only (access to A1 and U group parametersonly)1: User Parameters (access to a set of parameters selectedby the user)2: Advanced Access Level (access to all parameters)0 to 2 2 333A2-01toA2-32PreferredParameters1 to 32Parameters selected by the user are stored to the UserParameter menu. This includes recently viewed parametersor parameters specifically selected for quick access.If parameter A2-33 is set to 1, recently viewed parameterswill be listed between A2-17 and A2-32. Parameters A2-01through A2-16 must be manually selected by the user.If A2-33 is set to 0, then recently viewed parameters willnot be saved to the User Parameter group. The entire A2parameter group is now available for manual programming.b1-01 too2-08 – 334A2-33PreferredParameterAutomaticSelection0: Parameters A2-01 through A2-32 are reserved for theuser to create a list of User Parameters.1: Save history of recently viewed parameters. Recentlyedited parameters will be saved to A2-17 through A2-32 forquick access.0,1 1 334