B.2 Parameter Table366 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)◆ F: OptionsF parameters are used to program the drive to function with options.<21> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.<22> Parameter can be changed during run.<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.<25> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.<26> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output FrequencyVoltage 2, are set to 0.0.<27> Setting units for this parameter are determined by o2-04, Drive/kVA Selection. Less than 11 kW: 2 decimalpoints, 11 kW and above: 1 decimal point.<28> When parameter A1-02 = 5-PM OLV Control, E3-13 Motor 2 Base Voltage will be equal to T1-03, Motor RatedVoltage, after Auto-Tuning the drive<35> Default setting is determined by the V/f pattern selected to parameter E1-03.<36> Default setting changes when using OLV Control for PM motors.<37> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.<38> If using a Yaskawa pico motor, the default setting is 1800 r/min.No. Name Description Range Def.ControlModeAddr.Hex Pg.V/fOLVPMF1: Simple PG V/f ParametersUse F1 parameters to set up the drive for Simple PG V/f control.F1 parameters are enabled only when using Simple V/f with PG control (H6-01 = 03).F1-02Operation Selection atPG Open Circuit(PGO)Sets stopping method when a PG open circuitfault (PGO) occurs. Refer to parameter F1-14.0: Ramp to Stop - Decelerate to stop using theactive deceleration time.1: Coast to Stop2: Fast-stop - Decelerate to stop using thedeceleration time in C1-09.3: Alarm only - Drive continues operation.0 to 3 1 A − − 381 —F1-03Operation Selection atOverspeed (OS)(for Simple PG V/f)Sets the stopping method when an overspeed(OS) fault occurs. Refer to F1-08 and F1-09.0: Ramp to stop - Decelerate to stop using theactive deceleration time.1: Coast to stop2: Fast - Stop - Decelerate to stop using thedeceleration time in C1-09.3: Alarm Only - Drive continues operation.0 to 3 1 A − − 382 —