9.5 Commissioning and Initialization1. Install your System 300S with your CPU.2. Wire the system by connecting cables for voltage supply and signals3. Connect your PROFINET IO controller with Ethernet.4. Switch on the power supply.ð After a short boot time, the CP is in idle.At the first commissioning respectively after an overall reset of the CPU, thePROFINET IO controller and the Ethernet PG/OP channel have no IP address.This function is supported only if the PROFINET IO controller is not yet configured. Youget valid IP address parameters from your system administrator. The assignment of theIP address data happens online in the Siemens SIMATIC Manager starting with version V5.3 & SP3 with the following proceeding:1. Start the Siemens SIMATIC Manager.2. Switch to "TCP/IP -> Network card .... " using ‘Options è Set PG/PC interface è ’.3. Open the dialog for initialization of a station with ‘PLC è Edit Ethernet node’.4. To get the stations and their MAC address, use the [Browse] button or type in theMAC address. The Mac address may be found at the front of the CPU.5. Choose if necessary the known MAC address of the list of found stations. To checkthis with [Blink] you may cause the MT LED to blink.6. Either type in the IP configuration like IP address, subnet mask and gateway. Oryour station is automatically provided with IP parameters by means of a DHCPserver. Depending of the chosen option the DHCP server is to be supplied withMAC address, equipment name or client ID. The client ID is a numerical order ofmax. 63 characters. The following characters are allowed: Hyphen "-", 0-9, a-z, A-Z7. Confirm with [Assign IP configuration].Directly after the assignment the PROFINET IO controller is online reachable using theset IP address data.Since the IP address data, which were assigned here, are deleted atPowerOFF, you have to take them to a project by means of the hardwareconfiguration, which is described next.Initialization of the Ethernet PG/OP channelAssembly and commis-sioningAssign IP address param-etersVIPA System 300S+Deployment Ethernet communication - PROFINETCommissioning and InitializationHB140 | CPU | 317-4PN23 | en | 18-01136