4. Click to ‘PLC è Download’ Download ® the dialog "Select target module" isopened. Select your target module and enter the IP address parameters of theEthernet PG/OP channel for connection. Provided that no new hardware configura-tion is transferred to the CPU, the entered Ethernet connection is permanentlystored in the project as transfer channel.5. With [OK] the transfer is started.System dependent you get a message that the projected system differsfrom target system. This message may be accepted by [OK].® Your project is transferred and may be executed in the CPU aftertransfer.5.11.3 Transfer via memory cardThe memory card serves as external storage medium. There may be stored several proj-ects and sub-directories on a memory card. Please regard that your current project isstored in the root directory and has one of the following file names:n S7PROG.WLDn AUTOLOAD.WLD1. Start the Siemens SIMATIC Manager with your project.2. Create with ‘File è Memory Card File è New’ a new wld file.3. Copy the blocks from the project blocks folder and the System data into the wld file.4. Copy the wld file at a suited memory card. Plug this into your CPU and start itagain.ð The transfer of the application program from the memory card into the CPUtakes place depending on the file name after an overall reset or PowerON.S7PROG.WLD is read from the memory card after overall reset.AUTOLOAD.WLD is read from the memory card after PowerON.The short flashing of the MC LED of the CPU indicates the transfer process.Please regard that your user memory serves for enough space for your userprogram, otherwise your user program is not completely loaded and the SF LEDgets on.Proceeding transfer viamemory cardVIPA System 300S+ Deployment CPU 317-4PN23Project transfer > Transfer via memory cardHB140 | CPU | 317-4PN23 | en | 18-01 63