10.8 TIA Portal - Project transferThere are the following possibilities for project transfer into the CPU:n Transfer via MPIn Transfer via Ethernetn Transfer via memory cardCurrently the VIPA programming cables for transfer via MPI are not supported. This isonly possible with the programming cable from Siemens.1. Establish a connection to the CPU via MPI with an appropriate programming cable.Information may be found in the corresponding documentation of the programmingcable.2. Switch-ON the power supply of your CPU and start the Siemens TIA Portal withyour project.3. Select in the Project tree your CPU and choose ‘Context menuè Download to device è Hardware configuration’ to transfer the hardware configu-ration.4. To transfer the PLC program choose ‘Context menu è Download to deviceè Software’. Due to the system you have to transfer hardware configuration andPLC program separately.For transfer via Ethernet the CPU has the following interface:n X5: Ethernet PG/OP channelSo that you may the according Ethernet interface, you have to assign IP address parame-ters by means of the "initialization".Please consider to use the same IP address data in your project for the CP 343-1.1. For the transfer, connect, if not already done, the appropriate Ethernet jack to yourEthernet.2. Open your project with the Siemens TIA Portal.3. Click in the Project tree at Online access and choose here by a double-click yournetwork card, which is connected to the Ethernet PG/OP interface.4. Select in the Project tree your CPU and click at [Go online].5. Set the access path by selecting "PN/IE" as type of interface, your network card andthe according subnet. Then a net scan is established and the corresponding stationis listed.6. Establish with [Connect] a connection.7. Click to ‘Online è Download to device’.ð The according block is compiled and by a request transferred to the targetdevice. Provided that no new hardware configuration is transferred to the CPU,the entered Ethernet connection is permanently stored in the project as transferchannel.OverviewTransfer via MPITransfer via EthernetInitializationTransferVIPA System 300S+ Configuration with TIA PortalTIA Portal - Project transferHB140 | CPU | 317-4PN23 | en | 18-01 163