A System specific event IDsÄ Chapter 5.20 ‘Diagnostic entries’ on page 81Event ID Description0x115C Manufacture interrupt for EtherCAT / PROFINET IOOB: OB numberZINFO1: Logical address of the slave station that triggered the interruptZINFO2: Interrupt type0: Reserved1: Diagnostic interrupt (incoming)2: Process interrupt3: Pull interrupt4: Plug interrupt5: Status interrupt6: Update interrupt7: Redundancy interrupt8: Controlled by the supervisor9: Enabled10: Wrong sub module plugged11: Recurrence of the sub module12: Diagnostic interrupt (outgoing)13: Cross traffic connection message14: Neighbourhood change message15: Synchronisation message (bus)16: Synchronisation message (device)17: Network component message18: Clock synchronisation message (bus)31: Pull interrupt component32: Vendor-specific interrupt min.33: Vendor-specific interrupt topology change127: Vendor-specific interrupt max.ZINFO3: CoE error code0xE003 Error in access to peripheryZINFO1: Transfer typeZINFO2: Periphery addressZINFO3: Slot0xE004 Multiple configuration of a periphery addressZINFO1: Periphery addressZINFO2: SlotEvent IDsVIPA System 300S+ System specific event IDsHB140 | CPU | 317-4PN23 | en | 18-01 167