5. Set in the register MPI the transfer parameters of your MPI net and type a validaddress.6. Switch to the register Local connection.7. Set the COM port of the PC and the transfer rate 38400baud for the MPI program-ming cable.8. Transfer your project via ‘PLC è Load to module’ via MPI to the CPU and save itwith ‘PLC è Copy RAM to ROM’ on a memory card if one is plugged.1. Connect your PC to the PROFIBUS jack of your CPU via a MPI programming cable.2. Load your project in the Siemens SIMATIC Manager.3. Choose in the menu ‘Options è Set PG/PC interface’.4. Select in the according list the "PC Adapter (PROFIBUS)"; if appropriate you haveto add it first, then click at [Properties].5. Set in the register PROFIBUS the transfer parameters of your PROFIBUS net andenter a valid PROFIBUS address. The PROFIBUS address must be assigned to theDP master by a project before.6. Switch to the register Local connection.7. Set the COM port of the PC and the transfer rate 38400baud for the MPI program-ming cable.8. Transfer your project via ‘PLC è Load to module’ via PROFIBUS to the CPU andsave it with ‘PLC è Copy RAM to ROM’ on a memory card if one is plugged.Transfer via PROFIBUS is available by DP master, if projected as masterand assigned with a PROFIBUS address before.Within selecting the slave mode you have additionally to select the option"Test, commissioning, routing".5.11.2 Transfer via EthernetFor transfer via Ethernet the CPU has the following interface:n X5: Ethernet PG/OP channeln X8: PROFINET IO ControllerSo that you may access the Ethernet PG/OP channel you have to assign IP addressparameters by means of the "initialization".Ä Chapter 5.6 ‘Hardware configuration -Ethernet PG/OP channel’ on page 491. For the transfer, connect, if not already done, the appropriate Ethernet port to yourEthernet.2. Open your project with the Siemens SIMATIC Manager.3. Set via ‘Options è Set PG/PC Interface’ the access path to "TCP/IP ® Networkcard .... ".Proceeding transfer viaPROFIBUS interfaceInitializationTransferVIPA System 300S+Deployment CPU 317-4PN23Project transfer > Transfer via EthernetHB140 | CPU | 317-4PN23 | en | 18-0162