5.3.4.2 FilterThe analog input part has a filter integrated. The parametrization of the filter happens inthe Siemens SIMATIC Manager via the parameter ‘Integration time’ . The default value ofthe filter is 1000ms. The following values can be entered:n ‘Input 0≙ Channel 0’‘Input 1≙ Channel 1’– ‘Integration time 2.5ms’ ≙ 2ms (no filter)– ‘Integration time 16.6ms’ ≙ 100ms (small filter)– ‘Integration time 20ms’ ≙1000ms (medium filter)By using the record set 1 of the SFC 55 "WR_PARM" you may alter the parametrizationin the module during runtime.The time needed until the new parametrization is valid can last up to 2ms.During this time, the measuring value output is 7FFFFh.Record set 1Byte Bit 7 ... Bit 0 Default0 Bit 7...0: reserved 00h1 Filtern Bit 1, 0: Analog input channel 0Bit 3, 2: Analog input channel 1– 00b: ‘Integration time 2.5ms’ ≙ 2ms (no filter)– 01b: ‘Integration time 16.6ms’ ≙ 100ms (small filter)– 10b: ‘Integration time 20ms’ ≙ 1000ms (medium filter)n Bit 7...4: reserved10h2...12 Bit 7...0: reserved5.4 Digital input5.4.1 Propertiesn 16xDC 24Vn Maximum input frequency– 10 inputs: 100kHz– 6 inputs: 1kHzn Interrupt functions parameterizablen Status indication via LEDsParameter hardware con-figurationParametrization duringruntimeVIPA System MICRODeployment I/O peripheryDigital input > PropertiesHB400 | CPU | M13-CCF0000 | en | 16-4790