Inspection of the gas heating section (models ARG/ARD)Exhaust hoods installedInspection of compressorsVerification that direction of rotation is correct2.2 Start-up DataElectrical dataRating plate ActualPower supplyCheck specifica‐tions in the Installa‐tion ManualControl voltageFan consumption (A)Consumption of condenser fan 1 (A)Consumption of condenser fan 2 (A)Consumption of compressor 1 (A)Consumption of compressor 2 (A)Consumption of supply fan (A)Electric resistor 1 (Optional)Electric resistor 2 (Optional)Cool and heat modesRefrigerant circuit. Compressor 1Mode ValueSubcooling (min. 8 K, max. 18 K) ºC Liquid pressure: _____ barLiquid temperature: _____ ºCSuperheat (min. 4 K, max. 10 K) ºC Suction pressure: _____ barSuction temperature: _____ ºCComplete liquid line checked in sight glassCorrect oil level checked in sight glassRefrigerant circuit. Compressor 2Mode ValueSubcooling (min. 8 K, max. 18 K) ºC Liquid pressure: _____ barLiquid temperature: _____ ºCSuperheat (min. 4 K, max. 10 K) ºC Suction pressure: _____ barSuction temperature: _____ ºCComplete liquid line checked in sight glassCorrect oil level checked in sight glassAir flow valuesm3/hDesignMeasuredUnit installation data 2Start-up Data 2.245