036-21216-003-A-020416 Unitary Products GroupTABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060MODELDHEPOWERSUPPLYHEATERACCESSORYMODELNUMBERSUPPLYAIRBLOWERMOTORFLAELECTRIC HEATERS TOTALUNITAMPACITYAMPSMAX.FUSESIZE1AMPSMAX.SIZEHACR2AMPSkW STAGES TOTALAMPS060208-3-602CE0450052536.04.0 1 11.0 26.0 40 402CE045007254 5.6 1 15.6 26.9 40 402CE04501025 8.0 1 22.1 35.1 40 402CE04501525 11.9 2 33.1 48.9 50 502CE04502025 15.9 2 44.2 62.7 70 702CE04503025 22.2 2 61.7 84.6 90 90230-3-602CE0450052546.05.3 1 12.7 26.0 40 402CE045007254 7.5 1 18.0 30.1 40 402CE04501025 10.6 1 25.5 39.4 40 402CE04501525 15.9 2 38.2 55.3 60 602CE04502025 21.2 2 51.0 71.2 80 802CE04503025 29.6 2 71.2 96.5 100 100460-3-602CE0450074643.06.8 1 8.2 14.0 20 202CE045010464 10.1 1 12.1 18.9 20 202CE045015464 13.6 1 16.4 24.2 25 252CE045020464 19.5 2 23.5 33.1 35 352CE045030464 28.8 2 34.6 47.1 50 501. Dual element, time delay type.2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.3. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17for fuse block accessories available for field installation.FIGURE 2 - FIELD POWER WIRINGFIGURE 3 - CONTROL WIRING COOLING ONLYRVYCGFRY1BY2THERMOSTAT1TERMINALSUNITTERMINALSTRIPTB124VOLTTRANSFORMERCOOLINGONLY(24VOLTTHERMOSTAT)124VOLTTHERMOSTAT2TH07701024IFTHEUNITHASANECONOMIZER,REMOVEJUMPERJ1FROMTERMINALS8AND10ONTHERELAYBOARDTOPREVENTSIMULTANEOUSOPERATIONOFTHECOMPRESSORANDTHEECONOMIZER.IFYOUWANTTOCONTROLTHEECONOMIZERONASECONDSTAGEOFCOOLING,USETHETHERMOSTAT2TH04701224.