036-21216-003-A-02046 Unitary Products GroupTABLE 2: CAPACITY RATINGS - COOLING / GAS HEATINGMODELARI RATINGS1 GAS HEAT CAPACITYCOOLING CAPACITY80 / 67-95°FSOUNDRATING2(dBels)INPUT(MBH)DOEOUTPUT(MBH)AFUE3(%)S.S.E.4(%)S.E.5(%)TEMP. RISE(°F)GASLINE SIZE(in. O.D.)MBH SEER6 EER7DHG036N040 42.5 12.25 11.1 86 50 40 80.0 81.6 77.3 15-45 1/2DHG036N079 42.5 12.25 11.1 86 100 79 80.5 80.8 77.9 40-70 1/2DHG048N060 46.5 13.20 11.40 87 75 59 80.9 81.6 77.3 25-55 1/2DHG048N099 125 99 80.3 80.6 77.9 45-75 1/2DHG060N079 57.0 12.20 10.60 86 100 79 80.5 80.8 73.6 25-55 1/2DHG060N099 125 99 80.3 80.6 77.9 35-65 1/21. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.2. Rated in accordance with ARI Standard 110, utilization range “A”.3. AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.4. S.S.E. = Steady State Efficiency. (Percent Output)5. S.E. = California Seasonal Efficiency - determined in accordance with test procedures as specified by the State of CaliforniaEnergy Commission. Furnaces are available with a low NOx accessory.6. SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for coolingdivided by the total electric power input in watt-hours during the same period.7. EER = Energy Efficiency Ratio - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts at any given set ofrating conditions, expressed in BTUH per watt (BTUH/watt).TABLE 3: SOUND POWER RATINGS1UNITSIZE CFM ESP BLOWER SOUND POWER (dB 10-12 Watts)OCTAVE BAND CENTERLINE FREQUENCY (Hz) SWLdB(A)dBA@ 10 ft.2IWG SPEED kW 63 125 250 500 1000 2000 4000 8000036 1200 0.60 LOW 0.60 84 84 74 67 69 62 57 52 74 41048 1600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42060 2000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 431. These values have been accessed using a model of sound propagation from a point source into the hermispheric free field. ThedBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fanmanufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guaranteerequiring a dBA value or sound data in any other form than sound power level ratings.2. At a distance of 10 feet from the blower.TABLE 4: PHYSICAL DATA - BASIC UNITMODELS DHE/DHG036 048 060EVAPORATORBLOWERCENTRIGUGAL BLOWER (Dia. x Wd. in.)FAN MOTOR HP (BELT-DRIVE)12 x 101.5 12 x 101.512 x 101.5EVAPORATORCOILROWS DEEPFINS PER INCHFACE AREA (Sq. Ft.)4134.34135.14135.1CONDENSERFANPROPELLER DIA. (in.)FAN MOTOR HPNOM. CFM TOTAL241/24,500241/24,200241/24,200AIRFILTERS1QUANITY PER UNIT (15” X 20” X 1”)QUANTITY PER UNIT (14” X 25” X 1”)TOTAL FACE AREA (square feet)216.6216.6216.6SYSTEMCHARGE REFRIGERANT 22 (pounds/ounces) 10/8 10/*4 10/14COMPRESSOR QUANTITY PER UNIT (Hermetic Type) 1 / Recpt. 1 / Recpt. 1/Recpt.1. Filter racks are adapted for 1” or 2” thick filters.