036-21216-003-A-02048 Unitary Products GroupTABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 - 105°F - 115ºFAIR ONEVAPORATORCOILTEMPERATURE OF AIR ON CONDENSER COIL105°FTOTALCAP.1MBHPOWERINPUT2SENSIBLE CAPACITY3ENTERING DRY BULB, °FCFM WB°F 86 83 80 77 74 71 681500 72 47.6 3.65 32.3 27.8 23.3 18.9 14.4 #N/A #N/A67 42.5 3.56 39.0 34.5 30.0 25.6 21.1 16.6 12.162 38.0 3.49 38.0 38.0 36.6 32.1 27.6 23.1 18.757 37.4 3.54 37.4 37.4 37.4 32.9 28.5 24.0 19.51350 72 46.5 3.62 29.7 25.8 21.8 17.8 13.8 #N/A #N/A67 41.6 3.53 36.0 32.0 28.0 24.0 20.1 16.1 12.162 37.1 3.46 37.1 36.6 34.1 30.1 26.1 22.2 18.257 36.5 3.52 36.5 36.5 35.2 31.2 27.2 23.3 19.31200 72 45.4 3.60 27.2 23.7 20.2 16.7 12.2 #N/A #N/A67 40.6 3.51 33.0 29.5 26.0 22.5 19.0 15.5 12.062 36.2 3.44 36.2 35.2 31.7 28.2 24.7 21.2 17.757 35.7 3.49 35.7 35.7 33.0 29.5 26.0 22.5 19.01050 72 43.2 3.57 24.6 21.6 18.5 12.5 #N/A #N/A67 38.7 3.48 29.9 26.9 23.8 20.8 17.8 14.7 11.762 34.5 3.41 33.9 32.1 29.0 26.0 23.0 19.9 16.957 34.0 3.47 34.0 32.9 30.3 27.2 24.2 21.2 18.1900 72 41.1 3.54 22.0 19.4 16.8 14.3 11.7 #N/A #N/A67 36.7 3.45 26.8 24.2 21.7 19.1 16.5 14.0 11.462 32.8 3.39 31.5 28.9 26.4 23.8 21.2 18.7 16.157 32.3 3.44 32.3 30.1 27.5 24.9 22.4 19.8 17.2AIR ONEVAPORATORCOILTEMPERATURE OF AIR ON CONDENSER COIL115°FTOTALCAP.MBHPOWERINPUTSENSIBLE CAPACITYENTERING DRY BULB, °FCFM WB°F 86 83 80 77 74 71 681500 72 43.6 3.85 30.4 26.0 21.5 17.0 12.5 #N/A #N/A67 39.3 3.76 37.8 33.3 28.8 24.3 19.9 15.4 10.962 34.8 3.67 34.8 34.8 34.4 29.9 25.4 20.9 16.557 34.9 3.73 34.9 34.9 34.9 30.5 26.0 21.5 17.01350 72 42.9 3.83 28.0 24.0 20.0 16.0 12.0 #N/A #N/A67 38.6 3.74 34.8 30.8 26.8 22.8 18.8 14.9 10.962 34.2 3.66 34.2 34.0 32.0 28.0 24.0 20.0 16.057 34.3 3.72 34.3 34.3 32.9 28.9 24.9 21.0 17.01200 72 42.2 3.82 25.5 22.0 18.5 15.0 11.5 #N/A #N/A67 37.9 3.73 31.8 28.3 24.8 21.3 17.8 14.3 10.862 33.6 3.64 33.6 33.1 29.6 26.1 22.6 19.1 15.657 33.7 3.70 33.7 33.7 30.9 27.4 23.9 20.4 16.91050 72 40.1 3.78 22.9 19.9 16.9 13.8 10.8 #N/A #N/A67 36.1 3.69 28.7 25.7 22.6 19.6 16.6 13.5 10.562 32.0 3.61 31.6 30.0 27.0 23.9 20.9 17.9 14.957 32.1 3.67 32.1 30.9 28.2 25.1 22.1 19.1 16.0900 72 38.0 3.75 20.4 17.8 15.2 12.7 10.1 #N/A #N/A67 34.2 3.66 25.6 23.0 20.4 17.9 15.3 12.7 10.262 30.3 3.58 29.5 26.9 24.4 21.8 19.2 16.7 14.157 30.4 3.64 30.4 28.0 25.4 22.9 20.3 17.7 15.21. These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower PerformanceTable, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motorpower input is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.3. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this valueby 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.NOMINAL RATING ALL SENSIBLE CAPACITY