We reserve the right to make changes15FanInstallerSettings - Summer/winter OperationThe shift between summer or winter mode can be changed.Summer/winter Operation is set in the Temperature menu:• Summer/winter T (°C) You can set the temperature for the switch between winter and summer modes(factory setting: 12°C).• Sum./wint. T offset (°C) Offset temperature to switch between winter and summer modes(factory setting: 2°C).Example:14°C12°C10°CSetpoint for summer/winter operation of 12°C with an offset of 2°C means:Switches to summer operation at an outdoor temperature of ›14°C and to winter operation at ‹ 10°C.Settings - Temperature sensorTemperature sensor is set in the Temperature menu:• CP/T1 (°C) Outdoor temperature after pre-heating element• CP/T2 (°C) Air intake temperature before pre-heating element• CP/T3 (°C) Room temperature (Extract air temperature)• CP/T4 (°C) Discharge air temperature after counterflow heat exchanger• CP/T5 (°C) Condenser temperature• CP/T6 (°C) Evaporator temperature• CP/T7 (°C) Air intake temperature after heating coil• CP/T9 (°C) Heating coil temperature• TPanel (°C) Room temperature (control panel)See the temperature sensors' positions on the aggregate in the overview on page 6.Offset 2°COffset 2°C