40411) +-CMOD-0124V AC/DC + in24V AC/DC - inExternal power supply, 24 V AC/DC1)WARNING!Do not connect the +24 V AC cable to the control unit ground when the controlunit is powered using an external 24 V AC supply.■ Start-upSetting the parameters1. Power up the drive.2. If no warning is shown,• make sure that the value of both parameters 15.02 and 15.01 is CMOD-01.If warning A7AB Extension I/O configuration failure is shown,• make sure that the value of parameter 15.02 is CMOD-01.• set the parameter 15.01 value to CMOD-01.You can now see the parameters of the extension module in parameter group 15 I/Oextension module.3. Set the parameters of the extension module to applicable values.Examples are given below.Parameter setting example for relay outputThis example shows how make relay output RO4 of the extension module indicate thereverse direction of rotation of the motor with a one-second delay.SettingParameterReverse15.07 RO4 source1 s15.08 RO4 ON delay1 s15.09 RO4 OFF delayParameter setting example for digital outputThis example shows how to make digital output DO1 of the extension module indicate thereverse direction of rotation of the motor with a one-second delay.SettingParameterDigital output15.22 DO1 configurationReverse15.23 DO1 source1 s15.24 DO1 ON delay1 s15.25 DO1 OFF delay164 Optional I/O extension modules