• Unfasten the insertion ramp and attach the LCL filter module to bottom plate.• Attach the drive module pedestal guide plate to the cabinet bottom plate.• Attach the telescopic insertion ramp to the pedestal guide plate.• Remove the sheeting from the clear plastic shrouds (option +B051) of the drive modulefrom both sides.• Install the top metallic shroud to the drive module.• Install the back shrouds to the drive module.• To prevent the drive module from falling, attach its lifting lugs with chains to the cabinetframe.• Push the drive module carefully into the cabinet along the telescopic insertion ramp.Work preferably with help from another person as shown above. Keep a constantpressure with one foot on the base of the module to prevent the module from falling onits back.• Unfasten the insertion ramp and attach the drive module to the bottom plate.• Attach the LCL filter module and drive module to the punched section.• Attach LCL filter module to the side of drive module from top and bottom. Reinstall thecover.• Connect the LCL filter busbars to the drive module busbars with the connecting busbars.• Connect the LCL filter fan power supply cable to connector FAN3:LCL.• Connect the power cables and install the shrouds (option +B051) as described in sectionConnecting the power cables and installing the shrouds (option +B051) (page 86).• Connect the control cables as described in section Connecting the control cables to theinternal control unit (page 68).• Install the air baffles.Connecting the power cables and installing the shrouds(option +B051)Tasks (motor cables)StepInstall the grounding terminal to the drive module base.1Run the motor cables to the cabinet. Ground the cable shields 360 degrees at the cabinet entry.286 Installation example in Rittal VX25 cabinet