ACS850 More parameters read from drive to PLCParameter Description Setting Comment52.03 …52.12Actual value orparameter of driveGGii GG = parameter group, ii = parameter indexExample, 0104 = actual current; 0117 = motor temp 151.27 FBA PARREFRESHREFRESH Updates fieldbus settings (groups 50 to 53)ACS850 More parameters written from PLC to driveParameter Description Setting Comment53.03…53.12Parameter ofdriveGGii GG = parameter group, ii = parameter indexExample, 2202 = acceleration time 151.27 FBA PARREFRESHREFRESH Updates fieldbus settings (groups 50 to 53)Configuring ACS880 drivesStarting ACS880 drives for PROFIBUS DP1. Power up the drive.2. Enable the communication between the adapter module and the drive by setting parameter 50.01FBA A Enable to Enable.3. Select how the drive reacts to a fieldbus communication break with parameter 50.02 FBA A commloss func.Note: This function monitors both communication between the fieldbus master and the adaptermodule and communication between the adapter module and the drive.4. Define the time between communication break detection and the selected action with parameter50.03 FBA A comm loss t out.5. Select application-specific values for the rest of the parameters in group 50, starting from 50.04.6. Set the FPBA-01 configuration parameters in group 51. At the minimum, set the required nodeaddress in parameter 51.02 Node address and the communication profile in 51.05 = 1 (ABB drives).7. Define the process data transferred to and from the drive in FBA-01 configuration parameter groups52 and 53.Note: The adapter module sets the Status word and Control word automatically in parameters 52.01and 53.01.8. Validate the settings made in parameter groups 51, 52 and 53 by setting parameter 51.27 FBA parrefresh to Configure.9. Save the valid parameter values to permanent memory by setting parameter 96.07 Param save toSave.10. Set the relevant drive control parameters to control the drive according to the application.