37ACS880 Minimum required parameter settings for PROFINETThe minimum required parameter settings based on factory default settings.Parameter Description Setting Comment50.01 FBA A Enable Enable Activates fieldbus module.51.01 FBA A ype Ethernet Filedbus type.51.02 Protocol/Profile PNIO ABB Pro (11) Communication profile ABB drives.51.04 IP Configuration Static (0) -51.05 ...51.08IP address 192.xxx.xx.xx or any otherrequired IP address.-51.09 Subnet CDR 24 24 For subnet mask 255.255.255.0.51.27 FBA PARREFRESHREFRESH Updates fieldbus settings (groups 51to 55).20.01 Ext 1 commands Fieldbus A Fieldbus interface as source for startand stop.22.11 Speed ref1selectionFB A ref1 Fieldbus interface as source forspeed reference.31.11 Fault resetselectionP.06.01 bit 7 Fieldbus interface as source for faultreset.(46.01) Speed scaling [Scale max] Max speed/frequency scaling value(used in function block/visualizationinput SPEED_REF_MAX). Must beless or equal to drive parameter maxspeed/frequency.ACS880 More parameters read from drive to PLC (optional)Parameter Description Setting Comment52.03 …52.12Actual value orparameter of driveGGii GG = parameter group, ii = parameter indexexample, 0107 = actual current; 3501 = motor est.temp51.27 FBA PARREFRESHREFRESH Updates fieldbus settings (groups 50 to 57)