NEC RATINGSOutput ratingsApp.powerMax. cur-rentInput rat-ingFramesizeDrive typeACS580-07- Heavy-overload useLight-overload usePHdIHdPLdILdSNImaxI1hpAhpAkVAAA150240*200260203418260R80260A-4250302300361251542361R90361A-4300361**350414298542414R90414A-4■ DefinitionsNominal voltage of the drive. For the input voltage range, see section Electrical power network specific-ation (page 189).UNNominal rms input currentI1Nominal output current (available continuously with no over-loading)I2Apparent power (no overload)STypical motor power in no-overload usePNContinuous rms output current allowing 10% overload for 1 minute every 5 minutes.ILdTypical motor power in light-overload usePLdMaximum output current. Available for two seconds at start, then as long as allowed by drive temperature.ImaxContinuous rms output current allowing 50% overload for 1 minute every 10 minutes.IHd* Continuous rms output current allowing 30% overload for 1 minute every 10 minutes.** Continuous rms output current allowing 25% overload for 1 minute every 10 minutes.Typical motor power in heavy-duty usePHdNote 1: The ratings apply at an ambient temperature of 40 °C (104 °F).Note 2: To achieve the rated motor power given in the table, the rated current of the drivemust be higher than or equal to the rated motor current.The DriveSize dimensioning tool available from ABB is recommended for selecting the drive,motor and gear combination.Output derating■ Ambient temperature deratingDrive types other than ACS580-0414A-4 and ACS580-0430A-4In the temperature range +40…50 °C (+104…122 °F), the rated output current is deratedby 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplyingthe current given in the rating table by the derating factor (k):Technical data 151