0.00.51.01.52.02.53.0l (m)du/dtUN-------------(1/s)ÛLL /UNABÛLL /UNl (m)du/dtUN-------------(1/s)1.01.05.04.03.02.0100 200 300150 250 350500100 200 300150 250 350500Drive with du/dt filterADrive without du/dt filterBMotor cable lengthIRelative peak line-to-line voltageÛLL/UNRelative du/dt value(du/dt)/UNSelecting the power cables■ General rulesSelect the input power and motor cables according to local regulations:• Select a cable capable of carrying the drive nominal current. See sectionRatings (page 149) for the rated currents.• Select a cable rated for at least 70 °C maximum permissible temperature of conductorin continuous use.• Make sure that the inductance and impedance of the PE conductor/cable (groundingwire) are rated according to permissible touch voltage appearing under fault conditions(so that the fault point voltage will not rise excessively when a ground fault occurs).• 600 V AC cable is accepted for up to 500 V AC.Guidelines for planning the electrical installation 61