• Connecting external power supply wires for the cabinet heater (option+G300) (page 110)■ Grounding the outer shields of the control cables at the cabinet entryGround the outer shields of all control cables 360 degrees at the EMI conductive cushionsas follows (example constructions are shown below, the actual hardware may vary):1. Loosen the tightening screws of the EMI conductive cushions and pull the cushionsapart.2. Cut adequate holes to the rubber grommets in the entry plate and put the cables throughthe grommets and the cushions.3. Strip off the cable plastic sheath above the entry plate just enough to ensure properconnection of the bare shield and the EMI conductive cushions.4. Tighten the two tightening screws so that the EMI conductive cushions press tightlyround the bare shield.3241241413Note 1: Keep the shields continuous as close to the connection terminals as possible.Secure the cables mechanically at the entry strain relief.Note 2: If the outer surface of the shield is non-conductive:• Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors orthe grounding wire (if present).• Turn the shield inside out to expose its conductive surface.• Cover the turned shield and the stripped cable with copper foil to keep the shieldingcontinuous.Electrical installation 10511