Parameter setting example for frequency outputThis example shows how to make digital output DO1 of the extension module indicate themotor speed 0... 1500 rpm with a frequency range of 0...10000 Hz.SettingParameterFrequency output15.22 DO1 configuration01.01 Motor speed used15.33 Freq out 1 source015.34 Freq out 1 src min1500.0015.35 Freq out 1 src max1000 Hz15.36 Freq out 1 at src min10000 Hz15.37 Freq out 1 at src max■ DiagnosticsFaults and warning messagesWarning A7AB Extension I/O configuration failure.LEDsThe extension module has one diagnostic LED.DescriptionColorThe extension module is powered up.GreenOptional I/O extension modules 277