Operation75OperationWhat this chapter containsThis chapter describes:ï start-up and use of the driveï fault tracing of the line-side converterï control panel control of the line-side and motor-side converterï descriptions of ACS800-11/U11 specific parameters in the IGBT Supply ControlProgram (controls the line-side converter) and in the application program(controls the motor-side converter).For control panel use and motor-side converter fault tracing, see the appropriateapplication program firmware manual.Start-up and usePerform the start-up procedure as described in the appropriate application programfirmware manual. The parameters of the line-side converter control programneed not be set in a normal start-up procedure or in normal use. However, it isrecommended to set parameter 16.15 I/O START MODE to DI2 LEVEL:ï if the motor is started and stopped frequently. This prolongs the lifespan of thecharging contactor.ï when starting the motor without delay after the start command is required.ï If the drive is connected to a common DC bus. Otherwise, the charging resistormay be damaged.Noteï By default, the control panel controls the RMIO board of the motor-side converter(ID number 1). If the control panel is set to control the RMIO board of the line-sideconverter (ID number 2), the drive does not stop by pressing the control panelStop key in local control mode. Have the control panel control the RMIO board ofthe motor-side converter in normal use.ï Do not change the ID numbers of the converters from the default settings. If theID numbers of the line-side and motor side converters are set equal, the controlpanel stops communicating.