Technical data103SymbolsSizingThe current ratings are the same regardless of the supply voltage within one voltage range. To achievethe rated motor power given in the table, the rated current of the drive must be higher than or equal tothe rated motor current.Note 1: The maximum allowed momentary motor shaft power is limited to approximately 1.3 ∑ Pcont.max.If the limit is exceeded, motor torque and current are automatically restricted. The function protects theinput bridge and LCL filter of the drive against overload.Note 2: The ratings apply at an ambient temperature of 40∞C (104∞F). At lower temperatures theratings are higher (except Imax ).Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature isbelow 40∞C (104∞F) or the drive is loaded cyclically.DeratingThe load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres(3300 ft), or if the ambient temperature exceeds 40∞C (104∞F).Temperature deratingIn the temperature range +40∞C (+104∞F) to +50∞C (+122∞F) the rated output current is decreased 1%for every additional 1∞C (1.8∞F). The output current is calculated by multiplying the current given in therating table by the derating factor.Example If the ambient temperature is 50∞C (+122∞F), the derating factor is 100% - 1 ∑ 10∞C =90 % or 0.90. The output current is then 0.90 ∑ I2N or 0.90 ∑ I2hd.Altitude deratingIn altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m(328 ft). For a more accurate derating, use the DriveSize PC tool.Nominal ratingsIcont.max continuous rms output current. No overload capability at 40∞C.Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drivetemperature.Typical ratings:No-overload usePcont.max typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,230 V, 400 V, 500 V or 690 V.Light-overload use (10% overload capability)I2N continuous rms current. 10% overload is allowed for one minute every 5 minutes.PN typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,230 V, 400 V, 500 V or 690 V.Heavy-duty use (50% overload capability)I2hd continuous rms current. 50% overload is allowed for one minute every 5 minutes.Phd typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,230 V, 400 V, 500 V or 690 V.%∞CPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com