Safety instructions10OperationThese warnings are intended for all who plan the operation of the drive or operatethe drive.WARNING! Ignoring the following instructions can cause physical injury or death,or damage to the equipment:ï Before adjusting the drive and putting it into service, make sure that the motorand all driven equipment are suitable for operation throughout the speed rangeprovided by the drive. The drive can be adjusted to operate the motor atspeeds above and below the speed provided by connecting the motor directlyto the power line.ï Do not activate automatic fault reset functions of the Standard ApplicationProgram if dangerous situations can occur. When activated, these functionswill reset the drive and resume operation after a fault.ï Do not control the motor with the disconnecting device (disconnecting means);instead, use the control panel keys and , or commands via the I/Oboard of the drive. The maximum allowed number of charging cycles of the DCcapacitors (i.e. power-ups by applying power) is five in ten minutes.ï ACS800-04M, ACS800-07: Do not use the optional Prevention of UnexpectedStart function for stopping the drive when the drive is running. Give a Stopcommand instead.Note:ï If an external source for start command is selected and it is ON, the drive (withStandard Application Program) will start immediately after fault reset unless thedrive is configured for 3-wire (a pulse) start/stop.ï When the control location is not set to Local (L not shown in the status row ofthe display), the stop key on the control panel will not stop the drive. To stopthe drive using the control panel, press the LOC/REM key and then the stopkey .Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com